- Monitor and control of up to 200 dampers
- Control 2 network loops simultaneously
- Interface to fire alarm panels
- Up to 100 zones (via the use of a DIN08)
- LED & Physical Button Interface
Status & Control: Via the led & physical button interface the user can view the status of, and control all dampers on the system.
Network Optimisation: By networking any of our DCS damper control panels, the best, lowest cost solution can be achieved as dictated by the layout of the building.
Inter Panel Network: Prioritised messaging ensures that alarm messages are relayed as a priority between panels.
Large Network Capability: Individual panels are located anywhere on a communications loop of up to 3 kilometres in length.
Override Controls: During a fire alarm event options are presented to the user to override the automatic operation of the dampers.
Battery Backup: EN54-4 Compliant 2.3Ah internal battery. Hold up time of 2 hours.
BACnet: Add a BACnet BMS interface
Mechanical
Dimensions (WxHxD): 325.5mm x 410mm x 154mm
Connections: Cable gland knockouts on top side, gland plate on bottom
Doors: Left as standard (Can be on right by request)
Material: Powder coated mild Steel
Weight: ~8 Kg
Electrical
Supply: 90-264 VAC ; 47-63 Hz., 300W
Supply Wire Size: 1.3 – 2.5 mm² / AWG 16 – 14
Power consumption: 45W (max)
PSU approvals: EN 60950-1
Optional Battery Backup EN54-4 compliant 2.3Ah internal battery. Hold up time 2 hrs.
Fusing: Internal 1A a/s 20mm
Digital Inputs: 5V 10mA to volt free contacts, 4 off fitted as standard, 1 additional used for psu fail detect
When battery backed supply option selected.
Digital Outputs: 1 Opto-isolated 24V 100mA rated
– common fault signal normally
closed, open on fault.